Three Phase Kilowatt Hour Meter 100A With LCD Display KWH

  • 100A Kilowatt Hour Meter
  • Three Phase
  • 140mm(H) x 70mm(W) x 64mm(D)
  • Size of Connection clamp: 8 x 8mm
  • 2 Years Warranty

Download datasheet: LXEM3100 Datasheet

Compare

Description

Three Phase Kilowatt Hour Meter 100A With LCD Display KWH

The Three Phase Kilowatt Hour Meter 100A with LCD Display from Lanx Australis, one of Australia’s leading electrical distributors, is designed for a range of applications. It provides accurate energy monitoring for commercial, industrial, and residential settings, helping users track and manage power consumption effectively. With real-time data, it supports cost management by allowing better control of energy usage. The meter ensures reliable and precise metering, making it ideal for billing tenants, business units, or specific equipment. Additionally, it aids in energy audits to optimize power usage and efficiency. The easy-to-read LCD display offers clear visibility of power data, even in low-light environments, making it a practical choice for any installation requiring precise energy tracking.

Performance Criteria of Kilowatt Hour Meter

The Kilowatt Hour Meter is designed for optimal performance and reliability, meeting international standards. Here are the key performance criteria:

  • Operating Humidity: ≤75%
  • Storage Humidity: ≤95%
  • Operating Temperature: -10°C to +50°C
  • Storage Temperature: -30°C to +70°C
  • International Standard: Complies with IEC 62053-21
  • Accuracy Class: Class 1
  • Dust & Water Protection: IP51 rating
  • Protective Class: Insulating encased meter of Class II

Technical Data

  • Nominal Voltage: 240/415V AC (3~)
  • Operational Voltage: 161-300VAC
  • Insulation Capabilities:
    • AC voltage withstand: 4KV for 1 minute
    • Impulse voltage withstand: 6KV with 1.2µv waveform
  • Starting Current: 0.04A
  • Transitional Current: 1A
  • Minimum Current: 0.5A
  • Reference Current: 10A
  • Maximum Current: 100A
  • Current Measuring Range: 0.5 – 10(100)A
  • Peak Current Withstand: 3000A for 0.01s
  • Operational Frequency Range: 50-60Hz ±10%
  • Internal Power Consumption: ≤2W / 10VA per phase
  • Test Output Flash Rate (PULSE LED): 4000imp/kWh
  • Pulse Output Rate: 400imp/kWh

This kilowatt-hour meter is designed for efficient energy monitoring, with a wide current measuring range, high insulation capabilities, and compliance with international standards, ensuring accuracy and durability in any electrical setup.

Additional information

Weight 0.4 kg